KNX CO2-temp-fugt føler regulator sort

sch-product-heading-ean 5703472512297
sch-product-heading-type 70625 KNX AQS/TH-UP gl
Supplier Øvrige
sch-product-heading-productno 79.26.012.007
sch-product-heading-provideproduct sch-product-provide-article-s
sch-product-heading-instock Out of stock79.26.012.007
Arrival time (days) 12
sch-product-heading-sales-packaging-size 1
sch-product-heading-minimumsale 1
sch-product-heading-unit Stk
The Sensor KNX AQS/TH-UP gl measures CO2 concentration, temperature and humidity and calculates the dew point. The sensor can receive external measured values via the bus and process them with the own data to overall values (mixed values, e. g. room average).

The KNX AQS/TH-UP gl provides switching outputs with adjustable threshold values. The switching outputs and further communication objects can be linked by AND and OR logic gates. Additionally, an integrated actuating variable comparator can compare and output values that are received via communication objects.

Integrated PI controllers allows for control of a ventilation (depending on CO2 concentration and air humidity) and a heating/cooling system (depending on temperature).

The KNX AQS/TH-UP gl can emit a warning to the bus as soon as the area of optimum comfort (according to DIN 1946) is left.
Housing ABS plastic material
Colours similar to RAL 9005 jet black
Mounting In-wall (wall mounting in socket Ø 60 mm, 42 mm deep, resp. cavity wall socket for hole Ø 68 mm)
Protection category IP 20
Dimensions: Housing approx. 55 x 55 (W x H, mm), mounting depth approx. 8 mm,
base plate approx. 71 x 71 (W x H, mm)
Total weight approx. 53 g
Ambient temperature Operation 0 +50°C, storage -10 +60°C
Ambient air humidity max. 95% RH, avoid bedewing
Operating voltage KNX bus voltage
Bus current max. 20 mA
Data output KNX +/- bus terminal plug
Communication objects 196
CO2 measurement range 300...5000 ppm
Humidity measurement range 0% RH 95% RH